There are periods of time where the system seems to work fine and maintains a nice temperature range between 73-74.
I have an intermittent issue where the room temperature drops too low before the boiler fires again. My thermostat is set to 74 and the radiators will turn cold. Eventually the boiler will fire up again, but sometimes the delay is significant (1 hour?). During this time, the room temperature definitely drops below 74.
Notes:
I have an intermittent issue where the room temperature drops too low before the boiler fires again. My thermostat is set to 74 and the radiators will turn cold. Eventually the boiler will fire up again, but sometimes the delay is significant (1 hour?). During this time, the room temperature definitely drops below 74.
Notes:
- I have a high limit aquastat set to 190
- My thermostat is set to 74 permanently
- Cycles/hour = 3
- My circulator pump runs only when the boiler is firing. When the boiler stops, the circulator pump also stops.
- Aquastat turns on the boiler
- Thermostat turns on the circulator
- My thermostat seems to control the boiler
- The boiler controls the circulator