Lennox GSR14 Pulse. LPG. 60% in tank. Nothing is happening at furnace. No clicks, hums, nothing.
120 volts in. I have approx 29 volts across R and C but have approx 14 volts across W and C at thermostat terminals. Also checked at terminal strip in unit with demand on heat.
I replaced the transformer and the results are the same.
Earlier, while out walking my dog, I heard a loud pop so I assume a fuse on a pole blew somewhere. When I got home, there was no power. Local utilities were seen shortly and then power was back on shortly after that. Curious if this caused a problem with my Gas Energy Inc controller.
The secondary limit was tripped but resetting it did not help.
Thinking about jumping R to W but didn't want to try until after hearing something from the forum.
Thanks in Advance.