Good afternoon. I woke up to a cold house today so I checked the furnace and it has a low pressure fault code on it. I cycled power and tried it and my inducer motor won't turn on which I'm guessing is causing my low pressure fault. I checked for 120V power coming from circuit board terminals to the inducer motor on start up and get zero volts. I ran 120V test power to the inducer motor to confirm motor is good and it runs perfectly. So would it be safe to say I need to order a new control board?? The furnace is a ICP 2 stage furnace and its about 9yrs old. Thanks and appreciate and help!!
↧