EDR calculation check

$
0
0
I'm in the very early stage of planning/thinking about a basement reno. in a 90 yr old house. To make this work for headroom, I will need to remove the original 3" cast iron feed/return gravity loops and homerun PAP from each radiator to manifolds. (gas boiler) There is a lot more to consider but I would like to get a sanity check on my EDR calculation to start with. The radiators are the 5 tube type. There are also 3 in wall radiators that were not an exact match but I'm assuming the #'s are close enough for this purpose. I used this table from Utica. https://uticaboilers.com/sites/default/files/Radiation%20Tables.pdf The boiler is set at 160 which is 130 BTUH per sq ft emission. (Is this the right temp. to use?) The calculations are attached and here is a summary. Total EDR 77,178 1st Floor 1. Living room 1 = 7,608 BTUs 2. Living room 2 = 7,608 BTUs 3. Family room 1 = 7,608 BTUs 4. Family room 2 = 8,299 BTUs 5. Dining room = 8,991 BTUs 6. Hall = 7,881 BTUs 7. Kitchen - in wall = 1,170 BTUs 8. Bath - in wall = 910 BTUs 2nd Floor 9. Bedroom 1 = 6,370 BTUs 10. Bedroom 2 = 8,190 BTUs 11. Bedroom 3 = 11,375 BTUs 12. Bath - in wall = 1,170 BTUs How does this look? Thanks