2 gas heaters and 125k and 75k
Manual = Gas pressure to appliance controls must never exceed 14" W.C. (1/2 psi)
Utility States = The meter size at this address is 250. Which means it can handle up to 250,000 BTUs.
Meter reads 5lbs but it also looks like it has a 250 cf/h
I was told the gas company personally came in and took a look at the gas heaters when there was no service. I was also told by a contractor that the meter is really high and each of the devices should have a regulator on it to bring it down?