White-Rodgers Universal Hot Surface Ignition Control: problem.............

$
0
0
Hello Furnace experts...... I just got done installing a White-Rodgers "Universal Hot Surface Ignition Control" in my old Weil-McLain VHE-6 furnace/boiler. The original controller called for in my VHE-6 manual has been replaced with this universal module. Installation seemed straight forward. Upon power up, the only thing that happened was an error code of three yellow blinks, which in the new unit's manual says: " Measure AC voltage between terminal L1 and TH. If voltage is approximately 145 vac, polarity is reversed; reverse secondary leads on control transformer. Correct reading should be approximately 95 VAC." I measured 39 VAC. And their suggestion of reversing the secondary leads of the 24vac control transformer doesn't make any sense......... as one side of the 24vac transformer output has always been hard wired to ground for the 30 years this furnace has been in service...... a) I looked on the White Rodgers website, and could not locate a tech support email address or phone number for this type of product............. Any suggestions of where I can call or email???? b) Does anyone have any suggestions as to what I might have done wrong..... Thank you,,,,,,,,,,, Chuck